Zhejiang Changkai Electrical Co., Ltd.
Main products:High Voltage Switchgear Panel,Low Voltage Switchgear Panel,Substation,Indoor Vacuum Circuit Breaker,Outdoor Vacuum Circuit Breaker
Products
Contact Us
  • Contact Person : Mr. Gene Pan
  • Company Name : Zhejiang Changkai Electrical Co., Ltd.
  • Tel : 86-0577-61730881
  • Fax : 86-0577-61730882
  • Address : Zhejiang,Yueqing,Dongfang Road East section Wengyang Industry Zone Yueqing
  • Country/Region : China
  • Zip : 325606

SF6 Circuit Breaker,used circuit breakers

SF6 Circuit Breaker,used circuit breakers
Product Detailed
1:used circuit breakers 2:outdoor type 3:dirtness resistance 4:spring mechanism 5:three-phase porcelain-pole structure

Company profile:

 China·ZheJiang ChangKai Electrical CO.,LTD was locate d at coastal zone of south of Zhejiang province, that is ,Beautiful Yandan mountain of scenery YueQing known as China Electric Municipality. It possesses one hundred and eighty employees in total, thirty percent of which is various of professional technician. The company has completely pass ed the ISO9001 Quality System certification and obtain ed the production license, CCC Authentication, testing certification. Right of self-supporting importing and exporting. 

The company conducts management principle that the Strong's collab o ration with the strong , utilizing internal resource and absorbing external advantage to greatest degree and establishes long-period collaboration and partner relationship with Xi'an high-voltage research institution , PingGao electric and ZheJiang University, which provides technical support for new product's exploration and market enlargement . Additionally, with the advanced testing equipments, consummate after -sell service, it has been awarded as advanced departm e nt and excellent enterprise by government for many years."ChangKai" products are obtain the highly praise form various, some of them are exported to Korea , Russia , Albania , Vietnam , B urma, etc. The company will insist on the management idea of "Creative sprit, unceasing struggle, seek for outstand, regard talents”, redound upon the clients with good products and considerate service.

  used circuit breakers

 Technical data:

LW36-72.5       outdoor high voltage AC SF6 circuit breaker
NameUnitValue
Rated voltagekV72.5
Rated power frequency withstand voltage(1min)To earthkVK·160
Between interrupterK·200
Rated thunder impulse withstand voltageTo earthK·350
Between interrupterK·410
Powerfrequency withstand voltage under zero gauge pressure of SF6(5min)K·84
Rated frequencyHz50
Rated currentA3150
Amplitude factor 1.5
Rated short-circuit breaking currentKA31.5
Rated short-circuit breaking current(peak)KA80
Rated short-circuit with stand currentKA31.5
Rated peak value withstand current80
Rated short-circuit durations4
Rated out-of-phase breaking currentKA8
Breaking current of close-in faultKA90%lk,75%lk
Rated line-charging breaking currentA10
Operating sequence O-0.3s-CO-180s-CO
Resistance of the main circuitμ Ω≤40
Rated gauge pressure of SF6(20°C)Mpa0.4
Minimum functional gauge pressure(20°C)Mpa0.35±0.03/0.30±0.03
Annual leakage rate of SF6 <0.5%
Amount of water of SF6(V/V)ppm≤150×10-6
Mechanical lifetimes10000
Electrical level of radio interferenceμ V≤500
Creepage distanceBetween interruptermm2585
To earth2248
Weight of the SF6kg8
Weight of the circuit breakerkg1300
note:external insulation level is changed by modified coefficient. Every 2000m of altitude, K=1.13;altitude3000m, K=1.28
mian technical data of structure
NameUnitValue
Auxiliary circuit voltageVDC220 or DC110
Thevoltage/current of the opening and closing coilsV/ADC110/4;DC220/2
Eenergy storage motorRated voltageVDC220,AC220/DC110,AC110
The range of normal working voltageV85%-110%
PowerW600
The energy storage time of motors≤15
The loop voltage of the heater and the lampVAC220
Rated voltage of the auxiliary switchVDC220,AC220
Rated current of the auxiliary switchA10
Contacts of the auxiliary switches 10 normal opened contacts and 10 normal closed contacts
Mechnical adjustment of the breaker
NameUnitValue
Center distance between polesmm1200
Strode length of the moving contactmm120+30 
Contact stroke length of the moving contactmm25+20
Length of the inter phaseoperating connecting rodmm110+30
Switch-off speedm/s4.2-5m/s
Switch-on speedm/s2.2-3m/s
Switch-off timems≤40
Switch-on timems≤100
Break timems≤60
Switch-on/off timems≤80
Switch-off/on timems300
The time difference of the opening of three phasesms≤2
The time difference of the closing of three phasesms≤3

Product display:

SF6 Circuit Breaker,used circuit breakers



Copyright Notice @ 2008-2022 ECOL Limited and/or its subsidiaries and licensors. All rights reserved.